The output printed on a radiator is measured with water at an average of 70 °C. At the cooler temperatures a condensing boiler or a heat pump runs at, the same radiator gives out less. Enter what the room loses and the temperatures your system runs at, and this works out the catalogue output to buy.
Use the estimate panel below to start from the room's size, or work the heat loss out wall by wall in the heat loss calculator, which links straight back here with the figure filled in. This is a planning estimate. It is not an MCS heat loss design; a heat pump installation needs one, and its radiators should be sized from it. It does not model pipework, TRVs or system balancing.
What heats the water
Heat pumps are usually designed with 5 °C between flow and return. Boilers run a wider 10 to 20 °C drop.
Add the rating of a radiator you already have to see whether it will cope, and at what flow temperature it would. Leave n at 1.3 unless the manufacturer gives another figure.
Radiators are tested to BS EN 442 with water going in at 75 °C and coming out at 65 °C, in a room at 20 °C. The average water temperature is 70 °C, 50 degrees above the room, and the output measured at that point is the "ΔT50" figure in every catalogue. Output falls faster than the temperature difference does, so a radiator at half the ΔT gives well under half the heat.
n is the radiator exponent from the manufacturer's test. Panel radiators sit between about 1.29 and 1.36; 1.3 is the standard assumption when the model is unknown (BRE's low-temperature design tool uses it), and Stelrad and Purmo state that their conversion tables use it too. Our factors match Stelrad's published factor table to within 0.7% and Myson's to within 1.5% (both read September 2026). BTU/h is the output in watts multiplied by 3.412.
If you do not know the room's heat loss, the estimate panel works it out from the room's size, how many of its walls face outside, what is above and below it, the loft insulation, and the age and construction of the house. It uses the same method and U-values as the heat loss calculator, with RdSAP's default window area for the age of house scaled to the room, and a 2.4 m ceiling (2.7 m for a house built before 1930) unless you enter one. Tested on all eight rooms of a 1930s semi calculated in full, with the outside wall length and loft insulation entered, it lands within 10%, and within 2% for the six rooms without an outside door. It does not ask about outside doors or a wall to a garage, so rooms with them read low. If you leave the outside wall length blank it assumes the longer walls face outside, which reads on the high side. If you leave the loft as usual for its age, the estimate takes RdSAP's default and reads high if yours has been topped up, low if it has less. For the worked example's living room, with its 3.6 m outside wall entered, it gives 1,469 W against 1,379 W calculated wall by wall, because it assumes a larger window and a more exposed floor; left blank, it takes the 4.2 m wall and gives 1,541 W.
The living room from the heat loss calculator example loses 1,379 W at 21 °C. With a heat pump running 45 °C flow and 40 °C return:
That is three times the room's heat loss, for example a 1.8 m triple convector at 600 mm high or two 1.2 m double convectors. On a condensing boiler at 70/50 the same room needs 1,961 W. The 600 by 1,000 mm double convector a lot of these rooms already have (1,732 W at ΔT50) gives 578 W at 45/40, 42% of what is needed; it would need about 65 °C flow to heat the room on its own.
At 45/40 each watt of heat loss needs three watts of catalogue rating, so each watt saved by insulation takes three watts off the radiator you need. The heat pump size calculator takes the same room totals and sizes the unit.
For a room at 21 °C and n = 1.3. Multiply the heat loss by the last column to get the catalogue output. * Log-mean temperature difference, used where the water cools a lot across the radiator (see below).
| System | Flow / return | ΔT | Factor | Heat loss × |
|---|---|---|---|---|
| Older boiler | 80 / 60 | 48.3* | 0.956 | 1.05 |
| Condensing boiler | 70 / 50 | 38.1* | 0.703 | 1.42 |
| Low-temperature boiler | 55 / 45 | 29 | 0.493 | 2.03 |
| Heat pump | 50 / 45 | 26.5 | 0.438 | 2.28 |
| Heat pump | 45 / 40 | 21.5 | 0.334 | 3.00 |
| Heat pump | 40 / 35 | 16.5 | 0.237 | 4.23 |
Some manufacturers work from the log-mean temperature difference instead of the simple average. With a 5 °C drop the two agree to about 1%. With a 20 °C drop, as at 70/50, the simple average overstates the output by about 3%, so where the return is much cooler than the flow (the return end less than 70% as far above the room as the flow end, the threshold Purmo and REHVA use) the calculator switches to the log-mean figure and tells you so. The 70/50 and 80/60 rows are for checking an existing system. New and fully replaced systems in England should be sized for a maximum flow temperature of 55 °C or lower (Approved Document L 2021, paragraph 5.10).
Start from the room's heat loss: the estimate panel works it out from the room's size, walls and windows, or you can calculate it wall by wall. Convert watts to BTU/h by multiplying by 3.412, then divide by the correction factor for your system's water temperature. A room losing 1,379 W (4,705 BTU/h) needs a radiator rated at 1,961 W, or 6,700 BTU/h, on a condensing boiler at 70/50, and 4,131 W, or 14,100 BTU/h, on a heat pump at 45/40. Rules of thumb based on floor area alone ignore the walls, windows and draughts that set the heat loss.
It is the difference between the average water temperature and the room temperature when the radiator was tested: 70 °C water in a 20 °C room. Every catalogue quotes output at ΔT50 so radiators can be compared. At any other temperature the output is the ΔT50 figure multiplied by (ΔT ÷ 50) raised to the power 1.3. At ΔT30 that is about 51%, and at ΔT20 about 30%.
Some rooms often do; all of them rarely do. Heat pump systems are usually designed for water at 45 to 50 °C or lower, and the lower it is the more efficiently they run. At 45 to 50 °C a radiator gives out roughly a third to a half of its catalogue rating. Radiators in older houses were frequently oversized, so some will already cope. Put the rating of the existing radiator into the calculator: it shows what it delivers at your chosen temperature and the lowest flow temperature at which it would heat the room.
It describes how quickly a radiator's output falls as the water cools, measured in the BS EN 442 test. Panel radiators are typically between 1.29 and 1.36, towel rails and column radiators a little lower. 1.3 is the standard assumption when the model is unknown. The difference between 1.3 and 1.34 is about 3% at heat pump temperatures, enough to change the answer only when a radiator is borderline.
Yes, to the next size that is at least the output shown, and check the manufacturer's own table for the exact model and height. Slightly oversized radiators cost little and let the system run cooler, which suits both condensing boilers and heat pumps. Grossly undersized ones leave the room cold on the coldest days or force a higher flow temperature for the whole house.
Continue with these related heating tools
Room-by-room heat loss in watts and BTU at your area's design temperature
Design heat load at your local design temperature and the nearest headline unit sizes to check
Heating load and, for a combi, the hot water flow that sets its size