A combi's size is usually set by the shower. Heating mains water as fast as it runs takes three or four times the power the radiators need. This calculator works out both loads from your house's heat loss and the hot water flow you want.
Start with the whole-house figure from the heat loss calculator, which links here with it filled in. This is a planning estimate. It is not an MCS heat loss design. The Gas Safe engineer who fits the boiler confirms the size, gas supply and flue, and a heat pump installation would need a full MCS design. It does not allow for heat lost from pipes and the cylinder, how far down the boiler can turn, or the size of the gas meter and pipe.
Heat loss carried over from the heat loss calculator.
8 °C is the January mains temperature and 41 °C the mixed shower temperature used in SAP, the government's energy model. Size for winter.
The heating side is the whole-house heat loss on the design day, in kilowatts. A house that loses 7,370 W needs a boiler that can deliver 7.4 kW to its radiators. Adding a large margin on top used to be common; a modern condensing boiler turns itself down to match the load, but one that is much too big spends mild days switching on and off.
If you do not have a heat loss figure, the estimate panel builds a notional house from its floor area, storeys, built form and age, and runs it through the same room-by-room method as the heat loss calculator. Its assumptions are a square plan, 2.4 m ceilings (2.7 m for a house built before 1930, unless you enter the height), RdSAP's default window area for the age of house, two external doors, and the air changes and room temperatures of a typical room mix. Unless you choose one, the loft takes RdSAP's default insulation for the age. If yours has been topped up the estimate reads high, and if it has less it reads low. We checked it against full room-by-room calculations of three test houses (a 1930s semi, a mid-terrace and a Victorian terrace), and it came out between 4% under and 6% over. It gives you a starting figure. Measure the rooms for one you can rely on.
4.186 kJ heats a litre of water by one degree. Multiply by the litres a minute, by how many degrees the water has to rise, and divide by 60 seconds. A combi has no store, so it has to do this while the tap runs. The formula agrees with the spec sheets. Worcester Bosch's specifier guide for the 30 kW Greenstar 4000 (read September 2026) gives 12.3 l/min at a 35 °C rise, and 12.3 × 4.186 × 35 ÷ 60 = 30.0 kW. Vaillant's and Ideal's figures agree to within 1%.
A system or regular boiler heats a cylinder instead, and its hot water load depends on how quickly you want the cylinder back to temperature. The flow at the tap does not come into it. The Health and Safety Executive's legionella guidance says hot water should be stored at 60 °C at least (hse.gov.uk, page updated 26 September 2024).
The 1930s semi in Leeds from the heat loss calculator's test set loses 7,370 W. With a combi and one mixer shower at 11 litres a minute, from 8 °C January mains to 41 °C at the head:
The same house with a system boiler and a 150 litre cylinder reheated in an hour: 150 × 4.186 × (60 - 8) ÷ 3,600 = 9.1 kW for the cylinder. With hot water priority, where the heating pauses while the cylinder reheats, the boiler needs the larger of the two: 9.1 kW. If the controls run both at once, the two add up to 16.4 kW, or 11.9 kW with a two-hour reheat.
Two showers at once from a combi would take 50.7 kW. The biggest combis are badged at 50 kW, but Worcester Bosch's product page gives its 45 and 50 kW models the same flow, 16 litres a minute at a 40 °C rise, which is about 45 kW. So a house that runs two showers together needs a cylinder, and the calculator treats anything over 45 kW of hot water as beyond a combi.
In a large or draughty house the heating can be the bigger load. The badge size does not tell you the heating output: the combis we checked from Worcester Bosch, Vaillant and Ideal (read October 2026) give between 19.8 and 33.8 kW to the radiators. So when the heating is the bigger load and is above 19.8 kW, the calculator gives the heating output to look for instead of naming a size, and above 33.8 kW it points to a system boiler. If you are weighing a heat pump instead, the heat pump size calculator uses the same heat loss figure, and the Boiler Upgrade Scheme checker shows the grant.
One whose hot water output keeps up with the showers you run at once, and whose heating output covers your heat loss. For one mixer shower at about 11 litres a minute on cold January mains that is around 25 kW, so a 26 to 30 kW combi. For a stronger shower, or a bath that fills faster, go up a size. The heating load is usually the smaller of the two: a 1930s three-bed semi loses about 7.4 kW on the coldest day.
Not directly. Tables that go by bedrooms or radiators are standing in for two things: how much heat the house loses and how many bathrooms might run at once. A well-insulated four-bedroom house can need less heating than a draughty two-bedroom Victorian terrace. Work out the heat loss and the hot water flow, and size the boiler from those.
The headline figure on a combi is its hot water output. Manufacturers often set the heating output lower, because few houses need anywhere near 30 kW for their radiators. Check the spec sheet for both numbers: the hot water one against your shower, the heating one against your heat loss.
A modern condensing boiler that is somewhat oversized is not a problem, because it turns its flame down to match the load. One that is much too big for the heating, particularly a system boiler with no hot water demand to justify the size, can switch on and off repeatedly in mild weather, which wastes gas and wears the boiler. Size the new boiler from the heat loss, and do not copy the old boiler's plate.
UK spec sheets quote litres a minute at a 35 °C rise, typically about 10 l/min for a 24 to 25 kW combi, 12 for 30 kW and 14 to 15 for 35 kW. In winter the mains is nearer 8 °C, so a 35 °C rise gives water at 43 °C, enough for a 41 °C shower. The calculator converts your flow into that 35 °C figure so you can compare it straight with the spec sheet.
Continue with these related heating tools
Room-by-room heat loss in watts and BTU at your area's design temperature
The radiator output to buy for a room, corrected for your flow temperature
Design heat load at your local design temperature and the nearest headline unit sizes to check
Add this free calculator to your website. Copy the code below and paste it into your page.